Panic or Fire exit hardware installation requirement in IBC

Publish Time: 2022-08-28     Origin: D and D Hardware

1010.2.9.3 Installation. Where panic or fire exit hardware is installed, it shall comply with the following:
1. Panic hardware shall be listed in accordance with UL 305.
2. Fire exit hardware shall be listed in accordance with UL 10C and UL 305.
3. The actuating portion of the releasing device shall extend not less than one-half of the door leaf width.
4. The maximum unlatching force shall not exceed 15 pounds (67 N)



For further information about door viewers, please click here.